Emerson GXT 10KVA Power Supply User Manual


 
Cable Installation
21
Figure 14 Connecting Maintenance Bypass to GXT10000T-240X
NOTE
1. SINGLE-SOURCE FEED—If feeding the Maintenance Bypass Cabinet from a single
source, the input connection may be made to either TB1 or TB2.
2. DUAL-SOURCE FEED—If feeding the Maintenance Bypass Cabinet from a dual source,
the UPS input supply connection must
be made to TB1 and the bypass input supply
connection must
be made to TB2. The jumpers between TB1 and TB2 must be removed.
TB4
TB2
TB1
TB3
TB5
G
G
G
G
G
G
1
1
2
3
4
4
L1
L2
L1
L2
N
N
Input Output External Battery
GXT10000T-240X
L1 L2
L1 L2 L1 L2
NFINITY MAINTENANCE BYPASS CABINET WITHOUT
T
RANSFORMER
N
240V
120V120V
32
GEC
Remove these three wires
for dual source
(see NOTE below)
Flexible
conduit
Flexible
conduit
Input 2
Input 1