4 Configuration Menu
Column 1 = System Up Time.
Column 2 = Modbus Master Register Number.
Column 3 = Direction of Packet: OUT = Packet Sent from the F3400/F1000 (Master Request).
Column 4 = Modbus Packet.
4.10.4 Reset Modbus Port
This link allows users to reset the Modbus port so that the contents of the polling registers will
be cleared.
4.10.5 F-Series Modbus Slave Register Map
Table 4.1
Output Registers
Register Description Range
40001-40032 Input #1-32 Value 0-65535
40033-40187 Reserved
40188-40193 MAC Address 0-65535
40194-40197 IP Address 0-65535
40198 Model No. 0-65535
40199 Firmware Version 0-65535
40200 Number of Alarms Present 0-65535
40201-40232 Input #1-32 Alarm Bitmap See Table 4.2
40233-40400 Reserved
40401-40432 Input #1-32 Configuration See Table 4.3
Table 4.2
Status Flags (Registers 40201-40232)
Bit Description
00 1 = High1 Alarm
01 1 = Low1 Alarm
02 1 = High2 Alarm
03 1 = Low2 Alarm
04 1 = Digital Alarm
Table 4.3
Status Flags (Registers 40401-40432)
Integer Description
0 Not Installed
1 Not Configured