4.4.4. Map Descriptor Example #1 – Read Pressure.
In this example a Map Descriptor is defined which controls the task of reading pressure data from the Setra Model 370 Digital
Pressure Gage. The task gets performed every 5.0 seconds. When a response is received the data is stored in the Data Array
called DA_PRESSURE stating at element zero (the offset). Each pressure reading requires the driver store 5 parameters and hence
the length of the Map Descriptor is 5. Refer to Appendix A for further information.
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Gage_Function, Length, Scan_Interval
Read_Press, DA_PRESSURE, 0, RDBC, Gage1, Pressure, 5, 5.0s
Reserves 5
elements of the
Data Array to
store response
data.
Unique names
assist config file
validation
debugging but
are not
necessary.
The name of a
Data Array in
which the
response data
will be stored
.
The 1
s
t
location
in the Data
Array which will
be used for
storage.
The name of a Node
defined in the CSV file.
The node name connect
the MD to a node which
in turn points to a
connection Thus the
driver knows what port
and port settings to use
to send the poll..
Tells the driver
to read the
current
pressure
measurement
from the Gage
Tells the driver
to schedule this
MD no more
often than 5
seconds.