Appendix C. Driver Error Messages
Message Notes and Corrective Action
Set370:#1 FYI. Use an
Array called <%s> to
expose diagnostic info.
This message is provided for information and may be ignored. Read
Appendix C.1 for more information.
Set370:#2a. FYI. MD
Length=%d assigned by
driver.
This message is provided for information and may be ignored. The
message is printed when the Map Descriptor length in the
configuration file has not been specified. The driver makes the
correction by itself. To stop this message being printed, modify the
configuration file to match the length reported in the message.
Set370:#3 Err. No Write
MD's allowed.
This Driver cannot be used to write to the Setra device. Remove
any Map Descriptors whose function requires the FieldServer to
write to the Setra device.
3
Set370:#4 FYI. MD
param=Address has no
meaning. Ignoring.
This message is provided for information and may be ignored. The
address parameter is ignored by the driver. To stop this message
being printed, remove the address parameter from the configuration
file.
Set370:#5 Err.
Diagnostic x
There are a few variations of this message. Note the variation and
report the error to FieldServer tech support. You cannot resolve this
error yourself. The error is printed when the driver executes a
diagnostic function used for QA testing.
Set370:#6 Err. Array too
short. DA=%s MD=%s
The Data Array associated with the reported MD is too short to store
all the data returned by the Setra Gage. Increase the length of the
Data Array and of the Map Descriptor.
3
Set370:#7 Err. Pressure
message can’t be
parsed. Abandoned!
The response to a pressure reading request cannot be parsed by the
driver. Use the connection view to check the number of protocol
errors. If they keep rising, then take a log and report the error to
FieldServer Tech Support. If the protocol errors are occasional then
ignore them.
4
Set370:#8* Err. Status
message can’t be
parsed. Abandoned!
The response to a status reading request cannot be parsed by the
driver. Use the connection view to check the number of protocol
errors. If they keep rising, then take a log and report the error to
FieldServer Tech Support. If the protocol errors are occasional then
ignore them.
Set370:#9 FYI. Default
to reading pressure.
A Map Descriptor is found which does not have the ‘Gage_Function”
specified. The driver assumes your intention was to read the Gage’s
pressure. If you wish stop this message being printed then modify
the configuration file and specify the ‘Gage_Function’ = ‘Pressure’.
3
Set370:#10 Err. DA=%s
too short. Act=%d
Rqd=%d MD=%s
This message is printed when the driver is configured as a Server.
The Data Array associated with the reported MD is too short to store
the message. Modify the MD length and the DA length and try
again.
3
3
Modify the configuration CSV file. Download the modified file to the FieldServer and reset the
FieldServer for the changes to take effect
.
4
Message is printed once and then suppressed. This is to prevent the error log filling with redundant
repetition and thus obscuring other important information
.