FS-8700-101_Setra Model 370 Digital Pressure Gage Manual Page 8 of 23
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
4.2. Client Side Connection Descriptors
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
1
Protocol Specify protocol used Setra370
Baud* Specify baud rate
110 – 115200, standard baud
rates only, 2400.
Parity* Specify parity Even, Odd, None, Mark, Space
Data_Bits* Specify data bits 7, 8
Stop_Bits* Specify stop bits
1
Handshaking*
Specify hardware handshaking
The Setra Model 370 does not support
handshaking.
RTS, RTS/CTS, None
Poll _Delay* Time between internal polls 0-32000 seconds, 1 second
Example
// Client Side Connections
Connections
Port, Protocol, Baud, Parity, Handshaking, Poll_Delay
P8, Setra370, 2400, None, None, 0.100s
4.3. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node
Up to 32 alphanumeric
characters
Node_ID
This commonly used parameter has no meaning for this driver and may be
omitted.
Protocol Specify protocol used Setra370.
Connection
Specify which port the device is connected
to the FieldServer
P1-P8, R1-R2
1
Example
// Client Side Nodes
Nodes
Node_Name, Protocol, Connection
Gage1, Setra370, P8
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.