FieldServer FS-8700-105 Computer Drive User Manual


 
FS-8700-105_National_Time_and_Signal_FACP Manual Page 24 of 25
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Message Interpretation and Corrective Action
status if Node_ID < 1 (%d) 1 to 32. It is possible that this message could get pointed
as a consequence of a single corrupted message. If this
error occurs frequently then call Tech Support after taking
a log.
NATS:#414 FYI. Cant store
Node status. DA required.
See Message #24
NATS:#42 Err. Node /
Panel=%d offline. Comms
Failed. Port=%d
This message is printed when a message is received that
reports that communication to the indicated panel has
failed.
You must review and inspect your FACP equipment to
resolve this problem.
NATS:#43 FYI. Node /
Panel=%d online. Port=%d
No corrective action is required. The message is printed
when a node that had been reported as having failed
communications has this state restored to normal.
NATS:#44 Err. DA=%s too
short. Required=%d
This message is printed when the driver tries to update the
node status using the Data Array specified by the
‘NATSfacp_Status_DA’ parameter on the connection.
The offset used is equal to the node number and the driver
has found that the DA is too short to store the status as the
required offset. Edit the configuration file, setting the DA
length to the required length printed in the message.
Typically you will set this length to 32 as there are 32
possible panels on a connection.
Download the modified config file to the FieldServer and
reset the FieldServer for your changes to take effect.