FS-8700-112 FCI 7100 Series Driver Manual Page 20 of 24
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Message Description
FCI7100:#12a Err. No MD's to store message
data.
FCI7100:#12b Err. No MD's to store message
data."
FCI7100:#13 Err. Msg was ignored. MD Required
for Storage.
A message arrived and the driver could
not find a place to store the data.
Perhaps you were not expecting this type
of event/this loop/sensor. If you are not
interested in the data then ignore the
message. Otherwise update the
configuration file.
3
FCI7100:#13a Err. Diagnostic 1);
FCI7100:#13b Err. Diagnostic 2);
FCI7100:#13c Err. Diagnostic 3);
Take a log. Try and repeat the event that
caused the message to be printed. Then
contact tech support.
FCI7100:#14 Err. <%s> file not found., md-
>mapdesc_name ) ;
FCI7100:#15 Err. Event Type=<%s> Not
recognized." , drv_bd->event_desc )
FCI7100:#16 Err. Point Type='%c'(%#x) Not
recognized. , drv_bd->point_identifier[0] , drv_bd-
>point_identifier[0] ) ;
If this error is repeated often it is possible
that a FCI firmware update as made the
driver unusable. Take a log and contact
tech support.
FCI7100:#17 Err. Loop=%d < 1. Rejected. ,
drv_bd->loop )
This message should only be printed if a
byte in a message has been corrupted. If
you notice it more than once then take a
log and contact tech support.
FCI7100:#18 Err. Loop Type='%c'(%#x) Not
recognized. , drv_bd->point_identifier[2] , drv_bd-
>point_identifier[2] )
If this error is repeated often it is possible
that a FCI firmware update as made the
driver unusable. Take a log and contact
tech support.
FCI7100:#19 Err. Relay=%d < 1. Rejected. ,
drv_bd->relay
FCI7100:#20 Err. Zone=%d < 1. Rejected. ,
drv_bd->zone"
This message should only be printed if a
byte in a message has been corrupted. If
you notice it more than once then take a
log and contact tech support.
FCI7100:#21 Err. Point Type not recognized
FCI7100:#22 Err. Undefined Point Type"
Valid Point Types are listed in section
4.4.2
3
FCI7100:#23 Err. Event Type not recognized
FCI7100:#24 Err. Undefined Event Type
Valid Event Types are listed in section
4.4.2
3
FCI7100:#25a Err. Address+Length>99. Length
Truncated
FCI7100:#25b Err. Address+Length>99. Length
Truncated
The maximum value for a sensor/module
is 99. The combination of address and
length specified produce a number > 99
3
FCI7100:#26 Err. Invalid Module number.
Expected 1..99
FCI7100:#27a Err. Invalid Loop number. Expected
1..10
FCI7100:#27b Err. Invalid Loop number. Expected
1..10
FCI7100:#27c Err. Invalid Loop number. Expected
1..10
Correct the configuration file
3
3
Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to
take effect.