FieldServer FS-8700-112 Computer Drive User Manual


 
FS-8700-112 FCI 7100 Series Driver Manual Page 22 of 24
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Appendix B.1. Driver Stats Exposed.
In addition to the standard FieldServer operating statistics the driver exposes certain key
stats in a Data Array if required. An upstream device can then monitor these stats.
Add the following to your configuration file to activate these stats.
// Expose Driver Operating Stats.
Data_Arrays
Data_Array_Name, Data_Format, Data_Array_Length
fci-7100-stats, UINT32, 200
The driver exposes stats based on a port handle. The offset specified in the table below
must be added to the handle number multiplied by 100. i.e. for port whose handle is 1 then
the driver will store the 1
st
stat at 1+100*1=101.
Stat Offset Description
#define FCI_7100_STAT_NO_PLACE_TO_STORE 1
Increments each time point data
is received but there is no Map
Descriptor to store the data
(any)
#define
FCI_7100_STAT_NO_PLACE_TO_STORE_ZONE
2
Increments each time point data
is received but there is no Map
Descriptor to store Zone data
#define
FCI_7100_STAT_NO_PLACE_TO_STORE_RELAY
3
Increments each time point data
is received but there is no Map
Descriptor to store Relay data
#define
FCI_7100_STAT_NO_PLACE_TO_STORE_LOOP
4
Increments each time point data
is received but there is no MD to
store the Loop data
#define
FCI_7100_STAT_NO_PLACE_TO_STORE_SENSOR
5
Increments each time point data
is received but there is no MD to
store the Sensor data
#define
FCI_7100_STAT_NO_PLACE_TO_STORE_MODULE
6
Increments each time point data
is received but there is no MD to
store the Module data
#define FCI_7100_STAT_EMPTY_MSG 7
Number of times that a message
line was was zero bytes long
(excluding the terminator)
#define FCI_7100_STAT_SHORT_MSG 8
Number of times that a message
line was was too short probably
a system id tag line
#define FCI_7100_STAT_NO_RESET 9
Increments each time a reset
was rcvd but no DA was reset
#define
FCI_7100_STAT_NO_PLACE_TO_STORE_PANEL
10
Increments each time point data
is received but there is no MD to
store data that cannot be
attributed to a zone, relay, loop,
sensor, module
#define FCI_7100_STAT_RCVD_MSGS 11
Increments each time a
message is received