4.2. Client Side Connection Descriptors
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
1
Protocol Specify protocol used SNP
Baud* Specify baud rate
110 – 19200, standard baud rates
only (Vendor limitation), 19200
Parity* Specify parity
Even, Odd, None, Mark, Space
Data_Bits* Specify data bits
7, 8
Stop_Bits* Specify stop bits
1
Handshaking*
Hnadshaking is not supported
None
Poll _Delay* Time between internal polls
0-32000 seconds, 1 second
Timeout
The timeout specified for the connection is used as the data link layer
timeout. It is also used as the timeout for each Map Descriptor if a timeout
is not explicitly defined for a Map Descriptor.
Example
// Client Side Connections
Connections
Port, Protocol, Baud, Parity, Handshaking, Poll_Delay
P1, SNP, 19200, Odd, None, 0.100s
GE Port Defaults
Series 90-30 PLC’s Series 90-70 PLC’s
Baud 19,200 19,200
Data Bits 8 8
Parity Odd Odd
Stop Bits 1 1
Max Link Idle Time 10 Secs 5 Secs
GE Port Capabilities
Baud 300, 600, 1200, 2400, 4800, 9600, 19200
Data Bits 8
Parity Odd, Even, None
Stop Bits 1, 2
Max Link Idle Time 1 to 60 Secs
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.