Hearth and Home Technologies WSK-MLT Switch User Manual


 
6
2.2 Wall Switch Button Operation
(Refer to Figure 7)
Flame Button
Button Press: Unit On / Flames High, Turns on auxiliary
power
• Button Press: Flames Low
Button Press: Unit Off / Flames Off, Turns off auxiliary
power
Fan / Blower Button
• Button Press: Fan High (“3”)
• Button Press: Fan Medium (“2”)
• Button Press: Fan Low (“1”)
• Button Press: Fan Off
Temperature Button
Button Press will toggle between Automatic and Manual
Operation
Press and Hold the button for 3 seconds to toggle between
Fahrenheit and Centigrade Temperature Display.
Automatic Operation: Controller will monitor temperature
and control unit according to the set point.
Manual Operation: Controller will not automatically change
settings.
SET
Set Temperature Button
• Button Press: Displays Set Point
• Use Up and Down Arrows to Adjust Set Point
• Press Set Button to Store New Set Point
Temperature Set Point can be adjusted between the ranges of:
45-90
0
Fahrenheit or 7-32
0
Centigrade
NOTE: The controller will turn off the replace at 2
0
F over
set point and turn it back on at 2
0
F below set point.
Up and Down Arrows
• Push to adjust set point temperature under automatic
control.
AUX
Auxiliary Button
• Button Press: Turns on auxiliary power
• Button Press: Turns off auxiliary power
Can be operated independently of all functions.
2.0 Operating Instructions
For units WITH factory installed rocker switch.
The ON/OFF rocker switch on the replace (located near
the gas valve) must be in the “OFF” position for use with
the WSK-MLT system. The ON/OFF rocker switch will NOT
function with this device on Intelli re (IPI) models except
during a power outage.
For units WITHOUT factory installed rocker switch.
The ON/OFF rocker switch now installed on the replace
must be in the OFF position for use with the IPI or stand-
ing pilot system. The ON/OFF rocker switch will only be
used to control the replace in a no-power condition. For
standing pilot systems use the rocker switch to turn the
replace on and off. When power is restored switch the
rocker switch to OFF. For IPI system refer to “Operation
Under Battery Power” for instructions.
After all connections are made and the control box is
grounded, plug power cord into the replace junction box.
The wall switch will be functional at this time.
Figure 7.
<>
2.1 Setting Flame Height/manifold pressure
(To be done by a quali ed service technician). Upon initial
power-up of this device, valve pressure must be set for
ame adjustment.
Loosen output pressure tap on valve and connect with
pressure manometer.
• Press ame button once (Fig. 7); replace will light with
ames on high.
Turn solenoid clockwise to increase pressure, counter-
clockwise to decrease pressure until manifold pressure
on high is 3.5” water column for natural gas (NG), 10.0”
water column for propane (LP).
Once pressure is achieved spin jam-nut on solenoid stem
tight against regulator face to prevent rotation. Do not
overtighten.
• Press ame button twice to turn replace off.
Remove manometer tube and tighten or close pressure
tap. Use a soap solution to carefully check the pressure
tap for leaks.
NOTE: The temperature displayed by the wall switch may
take up to 30 minutes to stabilize on initial power-up.
NOTE: Check control box and assure switch is in the “OFF”
position. This switch is only used on Intelli re (IPI) control
systems under battery operation.