ITT 801P5 Switch User Manual


 
Page 20 Installation and Operation Manual
ADDITIONAL FEATURES
To alter the settings of the Smart-Switch
TM
, press the [MENU] key
and use the [UP/DOWN ARROW] keys to move through the
menu.
Mode (MOD)
Mode allows you to choose between Standard and Window
Mode. After MOD is displayed, use the [SELECT] key to
enter the Mode submenu and use the [UP/DOWN ARROW]
keys to toggle between STD and WIN. Press the [STORE]
key to temporarily save your setting.
Delay (DELY)
This menu item allows you to delay the actuation and
deactuation of the relay switches controlled by the set points.
After DELY is displayed, use the [SELECT] key to enter the
submenu. Use the [UP/DOWN ARROW] keys to cycle
through the available delay times. Your choices are 0, 40,
100, 300, 1000, 3000 or 5000 mSec. Press the [STORE]
key to temporarily save your settings.
Display (DISP)
This item sets how often the pressure display is updated.
This can be useful when there is a lot of fluctuation in the
pressure reading. After DISP appears, use the [SELECT] key
to enter the submenu. Use the [UP/DOWN ARROW] keys
to cycle through the available display settings. This option
can be set at OFF, 0.5, 1.0, 2.0, 3.0, 4.0, or 5.0 seconds.
Press the [STORE] key to temporarily save your setting.
Password (PASS)
The Password function allows you to set a password to limit
access to all menu functions. After PASS is displayed, use
the [SELECT] key to enter the submenu. Use [SELECT] to
find the digit of the value you want to change. The digit will
blink. Use the [UP/DOWN ARROW] keys to change the
value of the digit. When the value is correct, press the
[SELECT] key. Use this procedure until all digits of the
password are changed to the correct values. Then press the
[STORE] key to temporarily save your setting.