Page 30 Installation and Operation Manual
Display Shows EROR
This message might appear while programming the 801P5
Smart-Switch
TM
. The meaning depends on what is being
programmed. Following are the possible causes and solutions.
Incorrect password entered
You have entered an incorrect password. Re-enter the
correct password. If you have lost or forgotten the password,
contact Neo-Dyn Customer Service for assistance.
Incompatible switch set points.
You have entered incompatible set points. Switch 1 and
Switch 2 are independent of each other; however, the
following rules apply to each switch:
The increasing set point must be at or below the Full Scale
Output (F.S.O.) value; it cannot be less than 2% of F.S.O.,
and it must be at least 1% of F.S.O. above the decreasing set point.
The decreasing set point must be no lower than 1% of
F.S.O.; it can be no higher than 99% of F.S.O.; and it must
be at least 1% of F.S.O. below the increasing set point.
The minimum deadband is 1% of F.S.O.
Re-enter the set points to conform to the requirements.