Liebert 1000A Surge Protector User Manual


 
Location Considerations
7
3.4 Altitude
The standard units are designed for full load operation up to 4000 feet (1200m) above sea level. See
Figure 1 for recommended deratings for altitudes greater than 4000 feet (1200m).
Figure 1 Recommended derating for high altitude operation
Operation at full load at a higher altitude can be accommodated in ambient temperatures less than
104°F (40°C) ambient. Figure 2 shows the maximum allowable ambient temperature for full load
operation at altitudes above 4000 feet (1200 m).
Figure 2 Maximum ambient temperature for full load operation at higher altitudes