Chapter 3 Operation 23
E1-20010329-C-1.0
Figure 3-7
Note
If the previous shutdown was resulted from termination of battery discharge because
of Utility failure, the automatic function will be activated when the Utility restores.
2, After the system is started up properly , apply the load gradually and monitor the
load condition through LCD, as shown in Figure 3-8:
Figure 3-8
3, In the event of load exceeding the rated capacity of the UPS, of 105% load , the
buzzer will beep every 0.5 second with corresponding load percentage indication .
Remove load accordingly so the UPS is not operating under overload condition.
Note
If the system transfers from Normal mode to Bypass mode for 3 times within 1 hour due
to overload, it will remain in Bypass mode for 1 hour and can't transfer back to Normal
mode till the overload is removed.
2. Start in Battery Mode
220.0V
OUTPUT VOLT
70.0
%
LOAD