Liebert GXT2 - 3X1 Power Supply User Manual


 
40 Appendix 3 Product Specification
E1-20010329-C-1.0
Capacity 10kVA 15kVA 20kVA
Model GXT2-3X1
-0100L
GXT2-3X1
-0150L
GXT2-3X1 -0200L
Bypass Voltage
120~253Vac
non- ECO mode
Efficiency in
Normal Mode
(100% Linear
Load)
> 89% > 89% > 89%
Efficiency in
battery mode
(100% Linear
Load)
> 88% > 88% > 88%
interrupt
time
Utility Failure 0ms
Transferring
between inverter
and Bypass
Synchronized
< 4ms
Voltage transient response At the Resistive Load from 0~100% or 100%~0, the Output dynamic
voltage change range is lower than 5% Rated Voltage. Transient recovery
time is less than 60ms.
Audible Noise
< 55dB
1m < 60dB2m
Display LCD
Safety Passed CCEE certification,complied with EN60950 and EN50091-1.
Highest Input Voltage :
Line Voltage 554Vac,1 hour
static
EMC Conduction:EN55022 Class A
Radiation: EN55022 Class A
Harmonic current:THD<25%
With input isolated transformer connected
Immunity EN61000-4-2.3.4.5.6.8.11 Level III
DC offset
Lower than
±500mVdc
MTBF(Inverter )
30000 hours
ambient temperature is 25
,rated condition
MTBF(System)
150000 hours
Response time + maintenance time should be less than 24
hours
MTTR (Board Maintenance)
1 hour
Board Maintenance
Insulation Resistance
> 2MW
500Vdc
dielectric Strength
Output to earth
Input to earth
2820Vdc,leakage current<3.5mA, 1min
with no arc and breakdown
Surge Protection Satisfy the IV type of IEC60664-1, that is the ability to withstand
1.2/50uS+8/20uS exceeds 6kV/3kA.
Protection Level IP21