Liebert GXT2 - 3X1 Power Supply User Manual


 
Appendix 2 Communication Port Description 37
E1-20010329-C-1.0
Dry Contact Communication Mode
Port Definition
Pin2 : When the Utility fails, this pin will change from OPEN to CLOSE, it is OPEN in normal state
Pin5 : When the battery voltage is low, this pin will change from OPEN to CLOSE, it is OPEN in normal state
Pin6 : When +5V voltage has been applied for 1 second, the UPS will shutdown
Pin4 : GND for signal
Pin7 : GND for signal
Other Pin: No wire connection
Dry Contact Communication Mode can perform the following functions
When the Utility fails, the Utility failure information is provided ;
When the battery capacity is going to be used up, battery low information will be
provided ;
Control the shutdown of UPS.
Relay Communication Mode
Port Definition
Signal
alarm Output signal , summary alarm , non shutdown
alarms only.
failure Output signal UPS fail , will shutdown or transfer to
bypass.
Bypass Output signal, power supplying mode
battery low Output signal, battery mode
shutdown input signal, UPS shutdown command