Operation 45
The alarm conditions that cause the History Status buffer to stop gathering new data are:
Note that the Emergency Off alarm will also freeze the SCC History Status buffer with the Auto Transfer to
Bypass alarm (if the load is on the UPS system when the alarm condition occurs).
The History Status buffer does not resume collecting new frames until the fault is cleared and the Alarm Reset
pad is pressed for 15 seconds (or until the screen clears).
SCC Module
Auto Transfer to Bypass DC Cap Fuse Blown
Output Over-Voltage DC Over-Voltage Shutdown
Output Under-Voltage Inverter Fault
Overload Transfer Low Battery Shutdown
Overload Shutdown
Over-Temperature Timeout
Rectifier Fuse Blown
Reverse Power
DISCONTINUED
PRODUCT