Liebert STS2 Power Supply User Manual


 
Touch Screen Display
98
13.2.1 Security
Because the STS2/PDU Color Graphical Display provides access to various configuration and moni-
toring choices, a password or key lockout switch may be used to protect access to certain changes,
including:
Change configuration settings
•Clear logs
Make a source transfer
Reset an alarm
Without entering the password or enabling changes with the key lockout switch, you still can:
View the display, including the mimic, status and event help
•View logs
View the startup and bypass procedures
Use the SILENCE button to turn off the audible alarm
Using the Optional Key Lockout Switch
An optional key lockout switch for the STS2/PDU enables or disables the ability to make changes on
the STS2/PDU. The key lockout switch is located on the front of the unit next to the display; it is
behind the front door but can be operated without opening the front door. See Figures 20 through 22
for location of the key lockout switch.
To disable the changes, turn the key to the top of the switch, toward the closed padlock.
To enable changes turn the key to the horizontal position, toward the open padlock.
Figure 65 Key lockout switch
Using the Password
If the unit is not equipped with a keylock, a password is required when you attempt to:
Save changes in the CONFIG menu choices.
Transfer sources.
Reset active alarms.
•Clear logs.
When a password is requested, a keyboard is displayed on the touch screen. After you enter the pass-
word, select OK.
The password is case-sensitive. Password access times out after ten (10) minutes and must be
re-entered to save changes. The time-out period cannot be changed.
To set or reset the password:
1. Select SYSTEM SETTINGS from the CONFIG menu.
2. Select SYSTEM ID form the SYSTEM SETTINGS menu.
3. Click PASSWORD. A keyboard is displayed.
4. Enter a password. The password must be four (4) alpha-numeric characters and is case sensitive.
5. Click OK.
Changes disabled