Liebert STS2 Power Supply User Manual


 
Touch Screen Display
102
To configure the setpoints for each source:
1. Select SOURCE 1/2 SETPOINTS from the User Settings dialog box. The Source 1/2 Setpoints
dialog is displayed.
Figure 68 Source setpoints
2. Select 1 to configure the settings for Source 1.
3. Configure the settings using the keypad or dialog box that is displayed when you touch a button.
4. Select 2 for Source 2.
5. Configure the settings, as described in step 3.
6. Select SAVE to keep the settings for both sources. The Setpoints dialog is closed and the User
Settings dialog is displayed.
7. Select MANUAL MAX XFER PHASE ANGLE. A keypad is displayed.
This setting configures the maximum allowed phase difference between the sources and applies to
all manual transfers as well as any auto retransfer.
a. Configure this setting with a range of +/- 1-30 degrees. The default setting is +/-15 degrees
and the resolution is 1 deg.
b. Select OK to save the setting. The setting is now displayed in the adjacent field in the User
Settings dialog box.
Table 17 Setpoint parameters
Button Range Default Comments
Fast UV Setting (%)
-10 to -30% of Nominal
voltage rating
-20% Set in increments of 1%.
Slow UV Setting (%) -5 to -20% -10% Set in increments of 1%.
Slow UV detection delay 1-60 cycles 5 cycles Units: Line Cycle
OV Setting (%) +5% to +20% +10% Set in increments of 1%.
OV Detection Delay 1-255 cycles 3 cycles Units: 1/4 Line Cycle
I-PK Xfer Lockout
0 – 3.0 multiplied by
the unit current rating.
2.5 Times Unit
Current Rating
I-peak xfer lockout detection point.
Units: Amps RMS. Select the HI or
LO buttons to configure your setting.