Liebert STS2 Power Supply User Manual


 
Communication Interfaces
91
Table 15 shows the various groups, the settings contained within and the type of value it requires.
Table 15 Group settings and values
Group Item: Description Value Type Value Notes
Group 1:
System
Ratings
1 Input Volts (PDU) Integer Set per system spec.
2 Volts Integer Set per system spec.
3 Current Integer Set per system spec.
4 Frequency Scaled Desired freq. x 10 (600 = 60 Hz)
Group 2:
System
Settings
1 Language Enumeration [Not supported at this time]
2 System Model Number String 14 Character max.
3 System ID Number String 8 Character max.
4 System Tag Number String 8 Character max.
5 System Order Number String 8 Character max.
6 Options_1 Bitpacked 14 Character max.
7 Autodial Primary Line String 20 Character max.
8 Autodial Secondary Line String 20 Character max.
9 Autodial Pager Number String 20 Character max.
10 Autodial Pager PIN String 10 Character max.
11 Modem Init String String 20 Character max.
12 Modem Baud Rate Enumeration 0 = 2400, 1 = 9600, & 2 = 19200 bps
13 Modem LGS Check - Day Bitpacked
14 Modem LGS Check - Time Bitpacked
15 Comms Options 1 Bitpacked See section 12.1.3.
16 Comms Options 2 Bitpacked See section 12.1.3.
Group 3:
User
Settings
1 SRC1 Fast Undervoltage Setpoint Integer In % of nominal below nominal
2 SRC1 Slow Undervoltage Setpoint Integer In % of nominal below nominal
3 SRC1 Slow Undervoltage Detect Delay Integer In number of lines cycles
4 SRC1 Overvoltage Setpoint Integer In % of nominal above nominal
5 SRC1 Overvoltage Detect Delay Integer In 1/4 lines cycles
6 SRC1 I peak Transfer Setpoint Integer x 10
7 SRC2 Fast Undervoltage Setpoint Integer In % of nominal below nominal
8 SRC2 Slow Undervoltage Setpoint Integer In % of nominal below nominal
9 SRC2 Slow Undervoltage Detect Delay Integer In number of lines cycles
10 SRC2 Overvoltage Setpoint Integer In % of nominal above nominal
11 SRC2 Overvoltage Detect Delay Integer In 1/4 lines cycles
12 SRC2 I peak Transfer Setpoint Integer x 10
13 Max. Transfer Phase Angle Integer In degrees
14 Output Frequency Deviation Integer Freq. in Hz x 10
15 ReTransfer Delay Time Integer In seconds
16 Horn Volume Integer Range: 1-10
17 Critical Option Enabling Bitpacked See section 12.1.3.
18 Non-Critical Option Enabling Bitpacked See section 12.1.3.
Group 4:
Event
Mask
Settings
1 to 63 Event Mask settings for faults Event Mask See section 12.1.3.
64 to 143 Event Mask settings for alarms Event Mask See section 12.1.3.