Liebert STS2 Power Supply User Manual


 
Touch Screen Display
104
PDU Setpoints
The PDU Setpoints option allows you to configure the following parameters for the PDU, shown in
Figure 69.
Load Voltage THD (%)
Neutral Current (% of nom)
Ground Current (A)
Load Bus Overcurrent (% of nom)
Figure 69 PDU setpoints
Table 18 shows the range of valid values, default values and resolution for each parameter.
System Settings
The System Settings choice under the Config menu displays another pop-up menu with three choices:
Comm Options
System Options
System ID
To access the System Settings menu:
1. Select CONFIG from the menu bar.
2. Select SYSTEM SETTINGS from the Config menu.
Table 18 PDU setpoints
Button Range Default Resolution
Load Voltage THD (%) 3.0% to 99.9% 15.0% 0.1
Neutral Current (% of nom) 10% to 200% 95% 1
Ground Current (A) 1.0A to 50.0A 5.0A 0.1
Load Bus Overcurrent (% of nom) 50% to 100% 100%