3.15 Epsilon STS™ Customization
Certain parameters can be customized as follows:
1. Press the <Menu> button.
2. Select <Setup>, then <Customization> using the function buttons marked or .
3. Confirm by pressing the function button marked
4. Enter the password (default factory password is “0 0 0”. Select Setup, then Password to change the
password).
Figure 3-6: Customization Screen.
Table 3-1: Customization Settings.
Parameter Factory setting Customization
Nominal Voltage (both sources) As specified by customer 208,220,240,440,480,575,600V
Overvoltage threshold +10% +5% to +20% (1% steps)
Undervoltage threshold -10% -5% to –20% (1% steps)
Nominal Frequency (both sources) 60 Hz 50 or 60 Hz
Over-frequency threshold +5% +1 to +10% (0.5% steps)
Under-frequency threshold -5% -1 to -10% (0.5% steps)
Phase error tolerance (between sources) ±15° ±1° to ±45° (1° steps)
Retransfer Automatic (YES) Manual (NO)
(return to preferred source after transfer)
For additional customization of your Epsilon STS
(e.g. to change the retransfer
time delay from the factory setting
of 10 seconds), we recommend that you contact our MGE Customer Support
(reference page QS-8)
.
Customization active
Nominal Voltage 480V
Overvoltage threshold 10%
Undervoltage threshold 10%
Nominal frequency 60 Hz
Over-frequency threshold 5%
Under-frequency threshold 5%
Phase error tolerance S1/S2 15°
Retransfer YES