Minuteman UPS MCP-E Power Supply User Manual


 
26
(These items may require optional software or hardware)
FUNCTION FACTORY DEFAULT DESCRIPTIONUSER CHOICES
EnglishEnglish
CONFIGURABLE PARAMETERS
AND SETTINGS
UPS ID MCP-E SERIES Up to 64 characters to
define the UPS
Use this function to uniquely identify the
UPS in your network configuration
Battery installation date Date of Manufacture Date of Battery Replacement-
day/month/year (xx/xx/xxxx)
Enter the current date when
replacing the batteries
Battery life in days Preset for 1826 days Enter up to 5 characters When replacing the batteries,
calculate the actual number of days in
use after manufacture date and then
enter this expected life for your
environment
Auto Restart:
Enable/Disable
Enabled User may Enable or
Disable Autorestart
When "enabled", the UPS will
automatically restart and operate in
normal AC mode after a low battery
shutdown and normal AC has returned
Set audible
alarm state
Enabled User may Enable or Disable
until Low Battery Warning
Enabled: The UPS will emit an
audible alarm every 10 seconds
when in the battery mode.
Disabled until Low Battery Warning:
Used when software is controlling the
UPS or to silence the alarm. In
this state, the UPS will not emit
an audible alarm until the unit
reaches low battery warning level.
Enable or Disable all
UPS functions
Disabled User is required to enable prior
to operation. The UPS will not
operate until enabled.
This is a safety feature to prevent
operation while packaged during
shipping.
Set Inverter Output
Voltage
120 vac on 120 volt units.
230 vac on 230 volt units.
120 volt units: 100,110,115,120
230 volt units: 220,230,240
Allows the customer to set the voltage
based on the environment in which the
unit will be installed. This voltage is
set via external dip switch. The dip
switch is on the rear panel of the unit.