FX2N-32DP-IF Profibus-DP Interface Unit Specifications 3
3-2
3.3 Performance Specifications
Table 3.3:Performance Specifications
Items Specifications
Maximum Number of Controllable
I/O Points
Maximum 256 points (see section 1.3)
Transmission data
(Maximum exchanged data length)
400bytes can be sent and received during one bus cycle.
(input: 200 bytes, output: 200 bytes)
Transmission Type Bus network
Connector
9 pin D-SUB Connector for Profibus-DP network
8 pin mini DIN
Connector for FX-20P-E or personal computer (MELSEC
MEDOC PLUS)
Supported Baud
Rates and Bus
Length (bps)
9.6k, 19.2k,
45.45k, 93.75k
1,200 m (3,937')
187.5k 1,000 m (3,281')
500k 400 m (1,312')
1.5M 200 m (656')
3M, 6M, 12M 100 m (328')
LED Indicators
POWER LED ON when AC power is supplied.
RUN LED
ON when 32DP-IF is exchanging data with extension I/O blocks/
units and special function blocks.
BF LED ON when a communication error is detected. (No data exchange)
DIA LED ON when notice of diagnostic data is detected.