Mitsubishi 2033D SERIES Power Supply User Manual


 
MITSUBISHI ELECTRIC 2033D SERIES UPS
MITSUBISHI
ELECTRIC
2033D SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-11
1.4 Specifications
The UPS name plate displays the rated kVA as well as nominal voltages and currents. The
name plate is located on the inside of the UPS front door.
TABLE 1.1 Power Specifications
Rated output
Power
Input voltage
3 phase / 3 wire
Bypass input voltage
3 phase / 3 wire
Output voltage
3 phase / 3 or 4 wire
30kVA / 24kW
50kVA / 40kW
80kVA / 64kW
480V
480V
480V
480V
480V
480V
208V or 480V
208V or 480V
208V or 480V
TABLE 1.2 UPS Module Information
UPS
[kVA]
CABLE
ENTRY
WIDTH
[in / mm]
DEPTH
[in / mm]
HEIGHT
[in / mm]
WEIGHT
[lb./ kg]
HEATING
[kBTU/h]
30 BOTTOM 33.9 / 860 31.5 / 800 70.9 / 1800 2060 / 930 9.1
50 BOTTOM 33.9 / 860 31.5 / 800 70.9 / 1800 1810 / 820 13.5
80 BOTTOM 33.9 / 860 31.5 / 800 70.9 / 1800 1990 / 900 21.6