MITSUBISHI ELECTRIC 2033D SERIES UPS
MITSUBISHI
ELECTRIC
2033D SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-12
TABLE 1.3 Detail of Specifications
Rated Output kVA 30 50 80
Rated Output kW 24 40 64
AC INPUT
Configuration 3 phase, 3 wire
Voltage 480 V +15% to -15% (-30% can be operated)
Frequency 60 Hz (45.4Hz to 65Hz)
Reflected Current THD 4% typ. at 100% load; 7% typ. at 50% load
STATIC BYPASS INPUT
Configuration 3 phase, 3 wire
Voltage 480 V +/-10%
Frequency 60 Hz
BATTERY
Type Lead Acid
Ride Through Application Specific
Nominal Voltage 480 Vdc
Minimum Voltage 401 Vdc
Number of Cells 240
AC OUTPUT
Configuration 3 phase, 4 wire
Voltage 120/208 V, 277/480 V
Voltage Stability +/-1%
Frequency 60 Hz
Frequency Stability +/-0.05% in free running mode
Power Factor 0.8 nominal
Power Factor range 0.8 - 1.0 lagging (within output kW rating)
Voltage THD 2% typical THD at 100% Linear Load
5% typical THD at 100% non-linear load
Transient Response +/-3% at 100% load step
+/-1% at loss/return of AC power
+/-3% at load transfer to/from static bypass
Transient Recovery 16.6ms
Inverter Overload 125% for 10 minutes, 150% for 1 minute
System Overload 1000% for 1 cycle (with bypass available)
Bypass Overload 150% for 1 minutes
ENVIRONMENTAL
Cooling Forced Air
Operating Temperature
32゚F ~ 104゚F (0゚C - 40゚C)
Recommended 68゚F - 86゚F (20゚C - 30゚C)
Relative Humidity 5% ~ 95% Non Condensing
Altitude 0 ~ 9000 feet No Derating
Location Indoor (free from corrosive gases and dust)
(PCB conformally coated for use in industrial environment)
Paint Color Munsell 5Y7/1 (Beige)