NEC 320Lc-R Server User Manual


 
3-2 Installing Server
Installation
This section describes installation of NEC Express5800/ft series.
Tower Model
IMPORTANT: NEC Express5800/ft series is a precision instrument. You should ask
maintenance personnel to install it.
Select a suitable site for tower model.
CAUTION
Observe the following precautions to use the equipment safely. There are risks
of a burn, injury, or damage to physical assets. For details, see “Notes for Safe
Handling” in Chapter 1.
Remove all modules before moving the equipment.
Do not install the equipment in non-designated places.
* It is recommendable to use the server in a room where
temperature can be kept between 15 and 25ºC.
Wall outlet within the
reach of supplied power
cord.
UPS to prevent momentary voltage drop due to power
failure or lightning *
* Optional. UPS is recommended for best use of
features of NEC Express5800/ft series.
Close enough to connect the
mouse and the display.
Floor or a level
and robust desk or
table
Clean and tidy room
Location with an open space of 1m or more
on the front side, 50 cm or more on the rea
r
side, and 15cm or more on the right and left
sides of the server. (The front bezel extrudes
about 50 mm from the right side of the
server when fully opened.)
Room that can maintain the following conditions:
[When operating]
Temperature: 10 to 35ºC*
Humidity: 20 to 80%
Temperature gradient: ±10ºC/hr
A
tmospheric pressure: 749 to 1040hpa
[When not operating]
Temperature: 5 to 40ºC*
Humidity: 10 to 80%
Temperature gradient: ±15ºC/hr
A
tmospheric pressure: 749 to 1040hpa
100V - 120 V or 200V - 240
V parallel bi-polar power
outlet with grounding