2-3SectionOptical Fiber Cable (APF/PCF)
8
Observe the following when soldering wires onto the connector.
1, 2, 3...
1. Place
heat-shrink tubing onto all wires far enough from the end so as to not
interfere with soldering.
2. Pre-solder all wires and connector terminals.
3. Solder
all wires, inserting 4 mm of the exposed 5 mm of wire into the connec
-
tor terminal.
4. Slide the heat-shrink tubing onto the soldered area and shrink into place.
Assemble the connector hood as shown in the following diagram.
Aluminum
foil tape
Boot
2-3 Optical Fiber Cable (APF/PCF)
Although
the
special characteristics of optical fiber call for care in connecting op
-
tical
devices, laying optical fiber cables basically does
not dif
fer from laying wire
cables.
All
OMRON PCF and the PF10l APF (length: 1 m) cables come with con
-
nectors
attached. Connectors for all other APF cables must be assembled by the
customer. Note the following precautions when handling optical fiber cables:
1, 2, 3...
1. Always turn the power off to the Link Adapter when connecting or discon-
necting an optical fiber cable.
2. Always
hold the connector when disconnecting an optical fiber cable; never
pull on the cable.
3. APF
and PCF connectors are designed to be inserted only in one direction;
do not try to force them in the wrong way.
4. Insert APF and PCF connectors until they lock into position.
5. Always place the protective caps on unused Link Adapter modules.
6. If
dirty
, clean connectors gently with a tissue or sanitary cotton, using ethyl
alcohol if necessary. Do not use any solvent other than ethyl alcohol.
Soldering