Omron C-series Network Card User Manual


 
3SectionRepeater Units
14
Repeater Unit RPT01-(P) must be used when the number of Optical Slave
Racks, Optical Transmitting I/O Units, I/O Link Units, and Link Adapters con-
nected
in series exceeds 32. Insert a Repeater Unit between the 32nd and 33rd
Units.
The example below shows an Optical
Slave Rack and Optical T
ransmit-
ting
I/O Units connected in series. Note that a Repeater Unit is inserted after the
total of these Units reaches 32. When I/O Link Units or Link Adapters
AL002-(P)E, AL005-(P)E or AL006-(P)E are used, each of them must also be
counted as one of the 32 Units.
CPU Rack
with Optical
Master
Optical
Slave
Rack
Optical
T
ransmitting
I/O Units
Optical T
ransmitting
I/O Units
Repeat-
er Unit
32 Units total
1
- 32 Units
Nomenclature and Indicator Lights
The on/off indicator stays lit while power is turned on. The reception indicator
flashes
when
the optical bidirectional module receives signals from either side.
The
transmission indicator flashes when signals are sent
to either side from the
optical bidirectional module.