Panduit DPOE24S1XY Network Card User Manual


 
PANDUIT® DPoE™ Power Patch Panel User’s Guide Issue 2.2
Part Number: PN378A
10
IMPORTANT:
The DPOE™ Installation Worksheet should be used to record pertinent
information when installing DPoE™ Power Patch Panel(s), particularly if the EM is
monitoring the network. (See page 29, Provisioning the Panel, for more
information on how this information will be entered in the EM.) The installer
should complete this worksheet.
Panel Mounting Procedure
WARNING:
Only trained and qualified service personnel should install or service
DPoE™ Power Patch Panels
WARNING:
Before installing or servicing DPoE™ Power Patch Panels or
communication wiring, be aware of the hazards with the associated
electrical circuitry.
Rack Mounting Instructions
1. Record the MAC address, printed on a
sticker on the back of the unit, by
writing it in the space provided on the
included Installation Worksheet
(PANDUIT part number PN377).
2. Slip the Wiring Template Label over
the rows of connectors on the back of
the DPoE™ Power Patch Panel,
making sure the proper wiring code is
facing out and that the writing is not
upside down. One side of the label indicates EIA/TIA 568A wiring, while the other side is EIA/TIA
568B wiring.
3. Using a screw from the US standard thread screw set denoted by “01881-38 REV 2,” attach the
green and yellow striped grounding strap to the panel via the unthreaded hole nearest the
power connector. Next, install the panel onto a grounded rack using the appropriate screw set
provided to ensure proper grounding between the panel and the rack. Finally, attach the loose
end of the grounding strap to the rack within the same position as the panel.
PANDUIT Structured Ground Kits for Data Center Rack Grounding can be used to properly ground
PANDUIT® NetRack Rack Systems and racks from most other manufacturers.
4. Using four of the enclosed metric or English screws, as appropriate, install the DPoE™ Power
Panel into the 19” rack at the planned rack position.
WARNING:
The supplied screws are part of a grounding system to ensure that the
DPoE™ Power Patch Panel is properly grounded to the rack.
USE ONLY THE SUPPLIED SCREWS TO ATTACH THE PANEL TO
THE RACK.
Record the rack space position on the Installation Worksheet.