50
SunTouch Pool and Spa Control System Installation and User’s Guide
BROWN
WHITE
BLUE
BROWN
WHITE
BLUE
BLACK
BLACK
Transformer Connections
High Voltage Wiring
The high voltage wiring section is located inside the SunTouch enclosure. The SunTouch system can be
connected either to 120 VAC or 240 VAC. The SunTouch system should be wired to receive continuous
power (connect directly to sub-panel). The maximum current rating is 820/410 mA at 120/240 VAC 60 Hz/50
Hz.
For the AC power wire into the SunTouch Power Center from the main circuit breaker at the house, use
a three conductor cable. Follow manufactures instructions when installing and testing of ground fault
circuit breakers (GFCB) and interrupters (GFCI).
Connect input AC wires to the SunTouch Power Center transformer wires as follows:
120 VAC: Connect one wire to the Brown/White wires and one wire to the Blue/Black wires. One wire
must be connected to the grounding bar (see page 45).
240 VAC: Connect one wire to Black wire and one wire to Brown wire. The White/Blue wires are
connected together. One wire must be connected to the grounding bar (see page 45).
240 VAC 120 VAC
¾" conduit knockout from main
power supply circuit breaker (No.
14 minimum AWG wire)
Three ½"conduit
knockouts for relays
and other equipment.
GROUNDING BAR (three
terminals for relays and one
for main AC ground wire)
Transformer wires
and source AC
power wires not
shown