Powerware IPK-0319 Network Card User Manual


 
Local Configuration
12
BestLink SNMP/WEB Adapter User’s Guide : LTM-1343 B Draft 10/03/2001
Set the IP Address, Gateway Address and MIB System Group
Use this function (option 1) to set the IP address, the gateway address, or the
management information base (MIB) parameters of the adapter, as listed in
Table 1.
Table 1. IP Address, Gateway Address, and MIB System Group Parameters
No. Function Description Example/Remark
1 IP Address IP address of the adapter 192.72.173.188
2 Gateway Address Default IP address of the network gateway 192.72.173.254
3 Network Mask Subnet mask setting 255.255.255.0
4 sysContact System contact string for MIB-2 (up to 255 characters) Powerware
5 sysName System contact string for MIB-2 (up to 255 characters) BestLink SNMP/WEB Adapter
6 sysLocation System contact string for MIB-2 (up to 255 characters) TEST LAB
7 SNMP/WEB card
version
Firmware version Information only
8 Ethernet address MAC address Information only
Set SNMP/WEB Card Control Group
For those users who intend to use BOOTP/DHCP, telnet, or secure HTTP in
order to configure, control, update, or manage the adapter, certain control
parameters must be enabled or disabled. Use this function to modify those
parameters (option
2).
NOTE To prevent unauthorized viewing of the web pages presented by the BestLink
SNMP/WEB Adapter, use this function to enable HTTP Security Control.
Set Write Access Managers
For those users who intend to use an SNMP-compatible network management
system (NMS) to manage the BestLink Adapter, the IP address of the
management station must be added in the list on the BestLink Adapter in
order to receive write access rights. Use this function to add or delete the IP
address of the management station (option
3).