23
2008 RuggedCom Inc. All rights reserved Rev104
3.7 IEEE 1613 Type Tests
IEEE Test
IEEE 1613
Clause
Description Test Levels
Enclosure Contact +/- 8kV
C37.90.3 9 ESD
Enclosure Air +/- 15kV
C37.90.2 8 Radiated RFI Enclosure ports 35 V/m
Signal ports +/- 4kV @ 2.5kHz
D.C. Power ports +/- 4kV
A.C. Power ports +/- 4kV
C37.90.1 7 Fast Transient
Earth ground ports +/- 4kV
Signal ports 2.5kV common mode @ 1MHz
D.C. Power ports 2.5kV common & differential mode @ 1MHz
C37.90.1 7 Oscillatory
A.C. Power ports 2.5kV common & differential mode @ 1MHz
Signal ports 5 kV (Failsafe Relay)
D.C. Power ports 5 kV
C37.90 6 H.V. Impulse
A.C. Power ports 5 kV
Signal ports 2kV AC(Failsafe Relay)
D.C. Power ports 2kV AC
C37.90 6 Dielectric Strength
A.C. Power ports 2kV AC
NOTES:
• If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During disturbance errors may occur but
recovery is automatic).
• If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During disturbance no errors will occur).
3.8 IEC Environmental Type Tests
Test Description Test Levels
Severity
Levels
IEC 60068-2-1 Cold Temperature Test Ad -40 deg. C, 16 Hours N/A
IEC 60068-2-2 Dry Heat Test Bd +85 deg. C, 16 Hours N/A
IEC 60068-2-30
Humidity (Damp Heat,
Cyclic)
Test Db 95% (non-condensing), 55°C, 6 cycles N/A
IEC 60255-21-1 Vibration Tests Fc 2g @ (10-150) Hz Class 2
IEC 60255-21-2 Shock Tests Ea 30g @ 11 ms Class 2
IEC 60529 (IPx6) Ingress Protection Water Jet 100l/m @ 2.5m as per 14.2.6 N/A
IEC 60529 (IPx7) Ingress Protection Water Submersion 30 min @ 1m as per 14.2.7 N/A
IEC 60529 (IP6x) Ingress Protection Dust Talcum 2kg/m3 for 8h as per 13.4 Cat. 1&2