Schneider Electric AP9631 Network Card User Manual


 
35UPS Network Management Card 2 User’s Guide
outlet groups option
Turn on, turn off, or restart outlet groups with this option.
Path: UPS > Control > outlet groups
(This screen page lists by name and state each outlet group that has been configured through the
Configuration - outlet groups option).
You can select any of the following actions (or no action) for each group. These are one-time actions.
When the state of the outlet group is off:
On Immediately
On with Delay: Turn on the group after the number of seconds configured as Power On Delay.
(see “Power On Delay”).
When the state of the outlet group is on:
Off Immediately
Off with Delay: Turn off the group after the number of seconds configured as Power Off Delay
(see “Power Off Delay”).
Reboot Immediately: Turn off the group immediately, then turn it on after the number of seconds
configured as Reboot Duration (see “Reboot Duration”) and Power On Delay.
Reboot with Delay: Turn the outlet group off after the number of seconds configured as Power
Off Delay, then turn it on after the number of seconds configured as Reboot Duration and Power
On Delay.
ups -c
GraceSleep
(command line
interface)
Puts the UPS into sleep mode (turns off power for a defined period of time):
• The UPS turns off output power after waiting the Maximum Required Delay to allow
time for PowerChute Network Shutdown to shut down its server safely, and its Shutdown
Delay. See “The shutdown option” on page 38.
• When input power returns, the UPS turns on output power after two configured periods of
time: its Sleep Time and Return Delay Time. See “The shutdown option” on page 38.
• For a synchronized control group action, the Management Card of the UPS initiating the
action waits up to the number of seconds configured as its Power Synchronized Delay for
enabled group members to regain input power before it starts the Return Delay. If all
group members have already regained input power, the Power Synchronized Delay
is
omitted. If all group members regain input power during the delay, the remainder of the
delay is cancelled. See the online help for information configuring the fields used in
synchronizing an SCG.
Put UPS In Bypass
and Take UPS Off
Bypass (user interface)
ups -b Enter
ups -b Exit
(command line
interface)
Controls the use of bypass mode, which allows maintenance to be performed at a Symmetra
UPS and some Smart-UPS models without turning off power at the UPS.
Action Definition