20 REFERENCE & INSTALLATION MANUAL
5.3 REASSIGN ZONES TO EXPANSION INPUTS (1728EX & 1728 ONLY)
Section [126]: General Options
Option [8] OFF = Reassign Zones to Expansion Inputs Disabled (default)
Option [8] ON = Reassign Zones to Expansion Inputs Enabled
Reassign Zones to Expansion Inputs changes the zone numbering to increase the number of expansion inputs that
can be displayed on 10-Zone LED Keypads. In installations that require using mostly the expansion inputs, such as
using wireless zones, the 10-Zone LED Keypads may be unable to display some of the zones. In the following table,
the effects of enabling this feature and Reassign Keypad Zone 2 (see section 5.2) are shown:
5.4 ZONE PROGRAMMING
After connecting a hardwired detection device to one of the control panel's or zone expansion bus module’s input
terminals or after setting up any wireless transmitters, define the associated zone's parameters. The Zone
Parameters define the type of zone, the zone's partition assignment and how the control panel will react when an
alarm condition occurs on that zone. These Zone Parameters are programmed into one section as detailed in Figure
5.1 on page 21.
In the 1728EX and 1728, only on-board zones 01 to 04 can be defined a Fire, Delayed Fire or a
Keyswitch zone. On-board zone 05 cannot
be programmed as such. In the 1738EX and 1738 the on-
board zones 01 to 07 can be defined a Fire, Delayed Fire or a Keyswitch zone.
Table 6:
Zone Display with 10-Zone LED Keypad
Option [8]: OFF Option [8]: ON
Option [8]: ON and
Option [7]: ON (Reassign Keypad Zone 2)
1728/EX 1728 1728/EX 1728 1728/EX 1728
NO ATZ WITH ATZ NO ATZ WITH ATZ NO ATZ WITH ATZ
Control Panel
Input 1 = Zone 1 Zone 1 & 6 Zone 1 Zone 1 & 3 Zone 1 Zone 1 & 3
Input 2 = Zone 2 Zone 2 & 7 Zone 2 Zone 2 & 4 Zone 2 Zone 2 & 4
Input 3 = Zone 3 Zone 3 & 8 N/A N/A N/A N/A
Input 4 = Zone 4 Zone 4 & 9 N/A N/A N/A N/A
Input 5 = Zone 5 Zone 5 & 10 N/A N/A N/A N/A
Keypad
Zone 1 = Zone 6 Zone 11 Zone 3 Zone 5 Zone 3 Zone 5
Zone 2 = Zone 7
Zone 12 Zone 4 Zone 6 N/A N/A
Expansion
Input 1 = Zone 8 Zone 13 Zone 5 Zone 7 Zone 4 Zone 6
Input 2 = Zone 9
Zone 14 Zone 6 Zone 8 Zone 5 Zone 7
Input 3 = Zone 10
Zone 15 Zone 7 Zone 9 Zone 6 Zone 8
Input 4 =
Zone 11 Zone 16 Zone 8 Zone 10 Zone 7 Zone 9
Input 5 =
Zone 12 N/A Zone 9 Zone 11 Zone 8 Zone 10
Input 6 =
Zone 13 N/A Zone 10 Zone 12 Zone 9 Zone 11
Input 7 =
Zone 14 N/A Zone 11 Zone 13 Zone 10 Zone 12
Input 8 =
Zone 15 N/A Zone 12 Zone 14 Zone 11 Zone 13
= not displayed on 10-Zone LED Keypads