Teledyne 460H Computer Monitor User Manual


 
2.4.3 Control Inputs
There are 2 digital control inputs on the I/O connector; they are labeled ‘Zero Input’ and
‘Aux Input.’ The control inputs are used for remote control of the M460H by a device
such as a PLC. These inputs are triggered by providing a contact closure or low
impedance current path between the Input and the Gnd pin. This can be done by using a
mechanical switch or isolated transistor type output from another device, such as a PLC.
Never connect a voltage level output from another device to these contacts. The
functions of the control inputs is summarized below in Table 2-2:
Table 2-2 Control Inputs
Input Description
Zero Input Zero Calibration
Aux Input Pressure Display
Zero Calibration Input:
The zero calibration input is used to initiate zero calibration from an external device.
This input performs exactly the same function as the ‘Zero’ buttons on the front panel.
Pressure Display Input:
The pressure display input is used to display the pressure on the front panel. This input
performs exactly the same function as the ‘Pressure’ buttons on the front panel.
P/N 03662D Teledyne API Model 460H O
3
Monitor Operator Manual - Page 16