35
1600EP Series Instruction Manual
Data Setting Screens (Cont’d)
The following screens show the setting procedure for setting the data variables. They are accessed from
the main ‘Data Setting screens’ (see page 33) when the SHIFT/SELECT key is pressed:
AUTO RETRAN: YES
TO CHANGE: SELECT
Shift
Select
Set
Monitor
+
AUTO RETRAN: YES
TO ACCEPT: SET
AUTO RETRAN: NO
TO CHANGE: SELECT
Shift
Select
Set
Monitor
+
AUTO RETRAN: NO
TO ACCEPT: SET
Loops through both
possibilities
Returns to Data Setting screens
(with new value applied)
Cont’d from Auto Retransfer
data setting screen page 33
REMOTE: BYPASS
TO CHANGE: SELECT
Shift
Select
Set
Monitor
+
REMOTE: BYPASS
TO ACCEPT: SET
KEY LOCK: EN
TO CHANGE: SELECT
Shift
Select
Set
Monitor
+
REMOTE: SYSDWN
TO ACCEPT: SET
Loops through both
possibilities
Returns to Data Setting screens
(with new value applied)
Cont’d from Remote Operation
data setting screen page 33
INT BATT TST: YES
TO CHANGE: SELECT
Shift
Select
Set
Monitor
+
INT BATT TST: YES
TO ACCEPT: SET
INT BATT TST: NO
TO CHANGE: SELECT
Shift
Select
Set
Monitor
+
INT BATT TST: NO
TO ACCEPT: SET
Loops through both
possibilities
Returns to Data Setting screens
(with new value applied)
Cont’d from Int Batt Tst data
setting screen page 33
COMM MODE: RS232
TO CHANGE: SELECT
Shift
Select
Set
Monitor
+
COMM MODE: RS232
TO ACCEPT: SET
COMM MODE: SNMP
TO CHANGE: SELECT
Shift
Select
Set
Monitor
+
COMM MODE: SNMP
TO ACCEPT: SET
Loops through both
possibilities
Returns to Data Setting screens
(with new value applied)
Cont’d from Comm Mode data
setting screen page 33
Set to YES, the unit will automati-
cally retransfer back to UPS mode
after transferring momentarily to by-
pass mode to prevent a sag in the
output due to an instantaneous load
change. If set to NO, the unit will
attempt to ride out the load change
an the output voltage could be
decreased momentarily.
Default setting is YES.
This setting selects the RS232 as the
communication port. SNMP is dis-
abled.
This setting selects the SNMP as the
communication port. RS232 is dis-
abled.
Default setting is SNMP.
Set to YES, the unit will perform a bat-
tery test the rst time the unit trans-
fers to On-Line. If Auto Run (see page
34) is set to YES then the battery test
will be done at power up.
Default setting is NO.
This setting uses the remote switch to
place the unit in bypass mode.
This setting uses the remote switch to
shut the output of the unit off. While
off, the On-Line LED will be ashing
and the LCD will display the mes-
sage:
OUTPUT SHUTDOWN
REMOTE OFF
The remote switch connection is on
the rear terminal block at terminals 16
and 17. The unit will transfer 2 sec-
onds after the switch opens.
Default setting is BYPASS.