Toshiba 1600EP Series Power Supply User Manual


 
42
1600EP Series Instruction Manual
UPS Protection System
System Protection Features
The following schematic shows the electrical locations of the protection devices on the UPS.
System Protection Functions
The following charts show the built-in system fault protection functions on all the UPS models.
BUILT-IN UPS FAULT PROTECTION FUNCTIONS
Protection Item Output Overvoltage Output Undervoltage Output Overload
LCD Message OUT-OV OUT-UV OVERLOAD
Cause
Control malfunction;
chip error
Control malfunction;
Fuse opened; Load issue
Overload – Short circuit at load
Operation Mode
After Fault
Bypass operation – Chopper and inverter are
stopped
Inverter OL: Transfer to bypass;
Bypass OL: Inverter, chopper
stopped
Audible Alarm Yes – Continuous buzzer
See Audible Alarm Functions on
page 26
Visible Alarm Red Fault LED on
Inverter OL: Fault lamp off
Bypass OL: Fault lamp on
Relay Contact
Alarm
Fault relay closed
Bypass relay closed
Fault relay open;
Inverter OL: Bypass relay closed
Bypass OL: Bypass relay open
Auto-retransfer No
Inverter OL: Yes if bypass is OK
Bypass OL: No
Overcurrent
Current Limit
Overload
Input
Abnormal
Low Battery
Level
Overheating
Overvoltage/
Undervoltage