Try these remedies for common APS problems before calling for help. Call Tripp Lite Customer Service at
(773) 869-1234 before returning your APS for service.
SYMPTOM PROBLEMS CORRECTIONS
APS does not provide APS not properly connected to Connect APS to utility power.
AC output (AC input present) utility power.
Circuit breaker is tripped. Reset circuit breaker.
APS shutdown due to excessive Turn APS “OFF”.Wait 1 minute and
battery voltage, indicating possible switch to “AUTO/REMOTE”.
charger failure. Line disconnected
to prevent permanent battery
damage.
APS is overheated. Check air circulation near vents.
APS is set to “OFF” Set APS to “AUTO/REMOTE” or
“CHARGE-ONLY”.
APS does not provide Operating Mode Switch is set Set Operating Mode Switch to “AUTO/
AC output (AC input absent) to “CHARGE ONLY”. REMOTE.”
Load or High Temperature fault. Turn APS “OFF”.Wait 1 minute.
Remove overload.Check that vents
are clear for air circulation.Switch
to
“AUTO/REMOTE”.
Excessive battery discharge. Check battery condition.
APS will not charge the Connected batteries are dead. Check and replace old batteries.
battery (AC input present) (All Battery Indicator lights will be
flashing slowly.)
Battery fuse* is blown. Check and replace fuse.
Battery cabling* is loose or degraded. Check and tighten or replace cabling.
APS charger failure. Turn APS “OFF”.Wait 1 minute and
switch to “AUTO/REMOTE”. If
automatic shutdown occurs, call
Tripp Lite Customer Service.
All APS Indicator Lights are This is normal if the APS is set
OFF (AC input absent) to “CHARGE-ONLY”
All APS Indicator Lights are Excessive battery discharge. Use an auxiliary charger* to raise
OFF (AC input is present or battery voltage.Check external battery
absent) connections and fuse. Automatically
resets when condition is cleared.
All APS Battery Indicator Excessive battery discharge. Use an auxiliary charger* to raise
Lights are slowly flashing. battery voltage. Automatically resets
when condition is cleared.
APS “LOAD” Battery Light Inverter shutdown because load Turn APS “OFF”.Wait 1 minute.
flashing is too high or temperature is too Remove overload.Check that vents
high. are clear for air circulation.Switch
to
“AUTO/REMOTE”.
All APS Battery Lights are High battery voltage shutdown Check all charging sources.Reset by
rapidly flashing during battery charging. cycling control switch to "OFF" then to
“AUTO/REMOTE”or “CHARGE-ONLY”.
APS red “BATTERY HI/MED/LO” Inverter shutting down due to low Prepare for loss of power to
light is flashing battery charge. connected equipment.