Tripp Lite Power Inverters Power Supply User Manual


 
6
DIP SWITCH GROUP B
LOAD SHARING/EQUALIZE BATTERY CHARGE
The “Load Sharing” Configuration DIP Switches, #1 and #2 of Group B (located on the front
panel of your APS; see Diagram 1, p. 35), should be set with a small tool according to the guide-
lines below. DIP Switch #3, Group B should be kept in the “UP” position when you are not equal-
izing your batteries' charges. DIP Switch #4, Group B can be set to allow your APS to charge
large battery systems faster.
Load Sharing
(DIP Switches #1, Group B & #2, Group B)
Your APS features a high-output battery charger that can draw a significant amount of power
from your line power source when charging at its maximum rate. If an APS is supplying its
full AC power rating to its connected load at the same time as it is charging, it could trip its
line source circuit breaker. Tripping this breaker will cut off AC power to your load and stop
battery charging.
To reduce the chance of tripping this breaker, select APS models may be set to automatically
limit their charger output to keep the sum of their AC load and charger power within their
circuit breakers’ rating.
This charger limiting function has four settings, allowing you to choose less charger limiting
for APS configurations with higher rated breakers. The figures below show how to set your DIP
Switches to select how heavy a load can be placed on your APS before charger limiting begins.
Configuration
continued
4321
Battery Charger Limiting Points
Most Limiting (#1 & #2 Up*): Charger limiting takes effect the
moment any load is applied; charger output falls gradually from full
output at no load to no output at full load.
Less Limiting (#1 Down & #2 Up): Charger limiting begins when the
APS's load reaches 33% of the APS’s load rating. Charger output falls
gradually from full output at 33% of the APS's load rating to about 33%
of full output at full load.
Least Limiting (#1 Up & #2 Down): Charger limiting begins at when
the APS’s load reaches 66% of the APS’s load rating. Charger output
falls gradually from full output at 66% of the APS's load rating to about
66% of full output at full load.
No Limiting (#1 & #2 Down): No charger limiting occurs at any load size.
* Factory default settings.
4321
4321
4321