5 – Wiring continued
5-4 AC Input/Output Wiring Instructions
5-3 Electrical and Cable Data
AC Input and Output (75°C Minimum Copper Wire)
MaximumCurrent ConductorDiameter Torque Force
54.3 amperes 4.6mm(#6AWG) 2.60N•m(23in•lb)
1
UseM3pan-headscrews
S5
to attach the cable attachment tray
A1
beneath the terminal block.
2
Route the AC input/output wiring through cable sleeves and route the cable sleeves through the knockouts in the terminal block cover
A2
.
Each input/output wire should terminate with a ring terminal.
3
Connecttheringterminalforeachinput/outputcabletotheappropriateinput/outputterminals.Tightentheterminalswithatleast2.60N•m
of torque.
4
Secure the input/output cable bundles to the cable attachment tray with the included mounting ties
A3
.
5
UseM3pan-headscrews
S5
to secure the terminal block cover
A2
over the terminal block.