Register Parameter Parameter Modbus Start 3 Ø 3 Ø 1 Ø 1 Ø
Number Address Hex 4 wire 3 wire 3 wire 2 wire
High Byte Low Byte
30001 1 Volts 1 (L1 – N 4W or L1 – L2 3W) 00 00 ✓✓✓✓
30003 2 Volts 2 (L2 – N 4W or L2 – L3 3W) 00 02 ✓✓✓X
30005 3 Volts 3 (L3 – N 4W or L3 – L1 3W) 00 04 ✓✓XX
30007 4 Current 1 00 06 ✓✓✓✓
30009 5 Current 2 00 08 ✓✓✓X
30011 6 Current 3 00 0A ✓✓XX
30013 7 Watts Phase 1 - Integra 1540 only 00 0C X ✓✓
30015 8 Watts Phase 2 - Integra 1540 only 00 0E X X
30017 9 Watts Phase 3 - Integra 1540 only 00 10 XXX
30019 10 VA Phase 1 - Integra 1540 only 00 12 X ✓✓
30021 11 VA Phase 2 - Integra 1540 only 00 14 X X
30023 12 VA Phase 3 - Integra 1540 only 00 16 XXX
30025 13 var Phase 1 - Integra 1540 only 00 18 X ✓✓
30027 14 var Phase 2 - Integra 1540 only 00 1A X X
30029 15 var Phase 3 - Integra 1540 only 00 1C XXX
30031 16 Power Factor Phase 1 - Integra 1540 only 00 1E X ✓✓
30033 17 Power Factor Phase 2 - Integra 1540 only 00 20 X X
30035 18 Power Factor Phase 3 - Integra 1540 only 00 22 XXX
30037 19 Phase Angle Phase 1 - Integra 1540 only 00 24 X ✓✓
30039 20 Phase Angle Phase 2 - Integra 1540 only 00 26 X X
30041 21 Phase Angle Phase 3 - Integra 1540 only 00 28 XXX
30043 22 Volts Ave 00 2A ✓✓✓✓
30047 24 Current Ave 00 2E ✓✓✓✓
30049 25 Current Sum - Integra 1540 only 00 30 ✓✓✓✓
30053 27 Watts Sum 00 34 ✓✓✓✓
30057 29 VA Sum 00 38 ✓✓✓✓
30061 31 var Sum 00 3C ✓✓✓✓
30063 32 Power Factor Ave 00 3E ✓✓✓✓
30067 34 Average Phase Angle - Integra 1540 only 00 42 ✓✓✓✓
30071 36 Frequency 00 46 ✓✓✓✓
30073 37 Wh Import 00 48 ✓✓✓✓
30077 39 varh Import 00 4C ✓✓✓✓
30085 43 W Demand Import 00 54 ✓✓✓✓
30087 44 W Max. Demand Import 00 56 ✓✓✓✓
30105 53 A Demand 00 68 ✓✓✓✓
30107 54 A Max. Demand 00 6A ✓✓✓✓
30201 101 V L1-L2 (calculated) 00 C8 X X
30203 102 V L2-L3 (calculated) 00 CA XXX
30205 103 V L3-L1 (calculated) 00 CC XXX
30207 104 Average Line to Line Volts 00 CE X X
30225 113 Neutral Current 00 E0 X ✓✓
30235 118 THD Volts 1 - Integra 1540 only 00 EA ✓✓✓✓
30237 119 THD Volts 2 - Integra 1540 only 00 EC ✓✓✓X
30239 120 THD Volts 3 - Integra 1540 only 00 EE ✓✓XX
30241 121 THD Current 1 - Integra 1540 only 00 F0 ✓✓✓✓
30243 122 THD Current 2 - Integra 1540 only 00 F2 ✓✓✓X
30245 123 THD Current 3 - Integra 1540 only 00 F4 ✓✓XX
30249 125 THD Voltage Mean - Integra 1540 only 00 F8 ✓✓✓✓
30251 126 THD Current Mean - Integra 1540 only 00 FA ✓✓✓✓
30255 128 Power Factor (+Ind/-Cap) 00 FE ✓✓✓✓
58