62
Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03
METASYS N2 application
Integra 1560/1580 Point Mapping table
Address Parameter Description Units
1 Voltage 1 Volts
2 Voltage 2 Volts
3 Voltage 3 Volts
4 Current 1 Amps
5 Current 2 Amps
6 Current 3 Amps
7 Voltage average Volts
8 Current average Amps
9 Power (Watts) Sum kW
10 VA Sum kVA
11 var Sum kvar
12 Power Factor average
13 Frequency Hz
14 Active Energy (Import) kWh
15 Reactive Energy (Import) kvarh
16 Watts Demand (Import) kW
17 Maximum Watts Demand (Import) kW
18 Amps Demand Amps
19 Maximum Amps Demand Amps
20 Voltage L1-L2 (calculated) Volts
21 Voltage L2-L3 (calculated) Volts
22 Voltage L3-L1 (calculated) Volts
23 Neutral Current Amps
24 Active Energy (Import) GWh
25 Reactive Energy (Import) Gvarh
The following parameters are available only on the Integra 1540
26 THD V1 %
27 THD V2 %
28 THD V3 %
29 THD I1 %
30 THD I2 %
31 THD I3 %
32 THD Vmean %
33 THD Imean %