G7 ASD Operation Manual 109
Jump Frequency #3
Program Special Control Parameters Jump Frequencies
Same as Jump Frequency #1 (F270) and is used when multiple frequencies
are to be jumped (see the plus-or-minus value setting at F275). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.
Direct Access Number — F274
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Jump Frequency #3 Bandwidth
Program Special Control Parameters Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #3
(F274).
Direct Access Number — F275
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency Processing
Program Special Control Parameters Jump Frequencies Jump
Frequency Processing
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See F270 for further information on the Jump Frequency settings.
Settings:
Process Amount (use PID feedback)
Output Frequency
Direct Access Number — F276
Parameter Type — Selection List
Factory Default — Process Amount
Changeable During Run — Ye s
Preset Speed #8
Program Pattern Run Control Preset Speeds 8
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed #8. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see
F018 for further
information on this parameter).
Direct Access Number — F287
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #9
Program Pattern Run Control Preset Speeds 9
This parameter assigns an output frequency to binary number 1001 and is
identified as Preset Speed #9. The binary number is applied to S1S4 of the
Control Terminal Strip to output the Preset Speed (see
F018 for further
information on this parameter).
Direct Access Number — F288
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Ye s
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
F274 F288