G7 ASD Operation Manual 109
Jump Frequency #3
Program ⇒ Special Control Parameters ⇒ Jump Frequencies
Same as Jump Frequency #1 (F270) and is used when multiple frequencies
are to be jumped (see the plus-or-minus value setting at F275). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.
Direct Access Number — F274
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Jump Frequency #3 Bandwidth
Program ⇒ Special Control Parameters ⇒ Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #3
(F274).
Direct Access Number — F275
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency Processing
Program ⇒ Special Control Parameters ⇒ Jump Frequencies ⇒ Jump
Frequency Processing
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See F270 for further information on the Jump Frequency settings.
Settings:
Process Amount (use PID feedback)
Output Frequency
Direct Access Number — F276
Parameter Type — Selection List
Factory Default — Process Amount
Changeable During Run — Ye s
Preset Speed #8
Program ⇒ Pattern Run Control ⇒ Preset Speeds ⇒ 8
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed #8. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
F018 for further
information on this parameter).
Direct Access Number — F287
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Ye s
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed #9
Program ⇒ Pattern Run Control ⇒ Preset Speeds ⇒ 9
This parameter assigns an output frequency to binary number 1001 and is
identified as Preset Speed #9. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
F018 for further
information on this parameter).
Direct Access Number — F288
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Ye s
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
F274 F288