160 G7 ASD Operation Manual
Position Difference Limit
Program Feedback Parameters Feedback Settings Position
Difference Limit
While operating in the Position Control mode, this parameter sets the
maximum allowed difference between the commanded position and resulting
position as indicated by encoder pulses.
Direct Access Number — F631
Parameter Type — Numerical
Factory Default — 16.0
Changeable During Run — No
Minimum — 0.1
Maximum — 6553
Release After Run Timer
Program Protection Parameters Brake Fault Timer
This parameter sets the time that the brake will hold after the Run command
criteria has been met.
Direct Access Number — F632
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Earth Fault Alarm Level
Program Protection Earth Fault Alarm Level
This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Alarm activation criteria.
Direct Access Number — F640
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Ye s
Minimum — 0
Maximum — 100
Units — %
Earth Fault Alarm Time
Program Protection Earth Fault Alarm Time
In the event that the Earth Fault Alarm activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the Earth Fault Alarm is
activated.
This parameter sets the start-time of the count-down timer.
Direct Access Number — F641
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Earth Fault Trip Level
Program Protection Earth Fault Trip Level
This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Trip activation criteria.
Direct Access Number — F642
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 100
Units — %
Earth Fault Trip Time
Program Protection Earth Fault Trip Time
In the event that the Earth Fault Trip activation criteria is met, a timer begins
to count down to zero. Upon reaching zero, the Earth Fault Trip is activated.
This parameter sets the start-time of the count-down timer.
Direct Access Number — F643
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 2.50
Units — Seconds
F631 F643