G7 ASD Operation Manual 139
Compensation Coefficient for Iron Loss
Program Special Control Parameters Special Parameters
Compensation Coefficient for Iron Loss
This parameter compensates for losses in the rotor-to-stator coupling of the
excitation and torque current energy.
Direct Access Number — F487
Parameter Type — Numerical
Factory Default — 105.0
Changeable During Run — Ye s
Minimum — 0
Maximum — 255
Voltage Compensation Coefficient for Dead Time
Program Special Control Parameters Special Parameters
Voltage Compensation Coefficient for Dead Time
This parameter adjusts the degree of voltage compensation during dead time by
increasing or decreasing the on-time of the programmed PWM just prior to the
start of the dead time.
Direct Access Number — F488
Parameter Type — Numerical
Factory Default — 163.8
Changeable During Run — Ye s
Minimum — 1.64
Maximum — 327.6
Dead Time Compensation (Enable)
Program Special Control Parameters Special Parameters Dead
Time Compensation
This parameter Enables/Disables the Dead Time Compensation function. The
Dead Time Compensation feature provides a smoothing of the on-off IGBT
signal that feeds the Gate Driver board during the off portion of the on-off
cycle.
Settings:
Enabled
Disabled
Direct Access Number — F489
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Ye s
Dead-time Compensation Bias
Program Special Control Parameters Special Parameters Dead-
time Compensation Bias
This parameter sets a bias for the Dead-time Compensation function. The
Dead-time Compensation feature provides a smoothing of the on-off IGBT
signal that feeds the Gate Driver board.
Direct Access Number — F490
Parameter Type — Numerical
Factory Default — 0.000
Changeable During Run — Ye s
Minimum — -32.768
Maximum — 32.767
Switching Frequency of Current/Voltage Control
Program Special Control Parameters Special Parameters
Switching Frequency between Current and Voltage Control
This parameter sets the threshold frequency at which ASD control is switched
between Current-control and Voltage -control.
Direct Access Number — F491
Parameter Type — Numerical
Factory Default — 40.00
Changeable During Run — Ye s
Minimum — 10.00
Maximum — 60.00
Units — Hz