132 G7 ASD Operation Manual
Torque Command Mode
Program Torque Setting Parameters Torque Speed Limiting
This parameter specifies whether the torque command function is to be used in
one direction or both (F/R).
Settings:
Fixed Direction
F/R Permitted
Direct Access Number — F429
Parameter Type — Selection List
Factory Default — Fixed Direction
Changeable During Run — No
Speed Limit (torque) Reference
Program Torque Setting Parameters Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the Torque Control mode. This
parameter sets the input terminal that will be used to control the allowable
speed variance.
Settings:
None
VI/II
RR
RX
RX2 (option)
Fixed
Direct Access Number — F430
Parameter Type — Selection List
Factory Default — None
Changeable During Run — Yes
Speed Limit Torque Level
Program Torque Setting Parameters Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the Torque Control mode. This
parameter sets the targeted speed. The plus-or-minus value (range) for this
setting may be set at
F432.
Direct Access Number — F431
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Speed Limit Torque Range
Program Torque Setting Parameters Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the Torque Control mode. This
parameter sets a plus-or-minus value (range) for the Speed Limit Torque Level
(
F431).
Direct Access Number — F432
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Speed Limit Torque Recovery
Program Torque Setting Parameters Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the Torque Control mode. This
parameter sets the response time of the system to torque change requirements.
Direct Access Number — F433
Parameter Type — Numerical
Factory Default — 0.20
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
F429 F433