ADCP-80-524 • Issue 1 • November 2001
Page 17
© 2001, ADC Telecommunications, Inc.
mounting brackets allow mounting with WECO 1.00-inch (2.54 cm) hole spacing or EIA 1.25-
inch (3.18 cm) hole spacing. The slotted mounting hole pattern in the mounting brackets
compensates for vertical rack differences and allows mounting the fuse panel in either 1.75- or
2-inch (4.45 or 5.08 cm) rack spaces.
1.23 Environmental Characteristics
The environmental characteristics of the PowerWorx Type 70 Series Power Distribution Fuse
Panel are listed in Table 1.
2 ACCESSORIES
The following accessories for the PowerWorx Type 70 fuse panel are available:
• Standard Type 70 fuses with current capacity of from 0.2 Amp to 10.0 Amps
•Cablemanagement bar with mounting screws. Provides cable tie points. Installed at rear
of fuse panel by fastening ends of bar to both sides of the panel
•Foursizes of two-hole compression lugs for #2, #4, #6, and #14 AWG wire for input
power connection
•Kitof perforated fuse value designation cards and plastic covers
•Kitof fused equipment designation cards, a card holder, and a plastic cover
Table 1. PowerWorx Type 70 Fuse Panel Environmental Characteristics
PARAMETER DESCRIPTION
Operating temperature –5° C to +50° C
Storage temperature –45° C to +85° C
Humidity range 0% to 95% humidity (non-condensing)
Altitude range –197 ft. (0.06 km) to 13,000 ft. (3.96 km) above sea level
Fire rating All components UL94-V1 or better
Acoustic noise 0 dBA above ambient
Heat dissipation (fully loaded
traditional panel)
40 watts maximum@ 65 A per bus, 80 watts maximum @ 130 A
total fuse panel load
Heat dissipation (no load) 1 watt per bus