ADCP-80-524 • Issue 1 • November 2001
Page 22
© 2001, ADC Telecommunications, Inc.
Figure 15. Cable Management Bar Installation (Uninterrupted Power Fuse Panel Shown)
4.5 Rack Mounting
The fuse panel can be mounted in either a 19- or 23-inch (48.26 or 58.42 cm) wide rack. Two
sets of mounting brackets, one set for 19-inch racks and one set for 23-inch racks, are provided
with the fuse panel. Eight 5/16-inch (7.94 mm) long, thread-forming, Phillips-drive, 8-32 flat-
head screws are provided for attaching the mounting brackets to the panel. Four 3/8-inch (9.53
mm) long, Phillips-drive, 12-24 pan-head screws (with #12 flat washers) are provided for
attaching the mounting brackets to the equipment rack.
Use the following procedure to install the fuse panel in the equipment rack:
1. Select the set of mounting brackets (19- or 23-inch) that correspond to the width of the
equipment rack into which the fuse panel will be installed.
2. Orient the mounting brackets as shown in Figure 16.
3. Attach the brackets to the sides of the fuse panel chassis using the eight 5/16-inch (7.94
mm) flathead screws provided. Tighten screws to 15 pound force-inches (1.7 Newton
meters) of torque to insure grounding.
4. Place the fuse panel in the specified mounting space within the rack.
5. Secure the panel to the rack as shown in Figure 17 using the four 3/8-inch (9.525 mm)
long pan-head screws and flat washers provided.
Caution: When attaching the cable management bar to the fuse panel, use only the hardware
supplied with the cable management bar. Use of any other hardware could cause contact with
internal parts of the fuse panel. If parts are missing, please contact ADC.
Note: A fuse panel with the cable management bar attached may exceed the 12-inch
(3.05 mm) overall depth objective described in GR-63 CORE, 02-14.
Caution: When attaching the mounting brackets to the fuse panel, use only the 5/16-inch (7.94
mm) long, black chromate finish, thread forming, flathead screws provided with the panel. Use
of any other hardware could cause contact with internal parts of the panel. If parts are missing,
contact ADC to order replacement parts.
16387-B
CABLE
MANAGEMENT
BAR
ATTACH TO
EITHER SET
OF 3 HOLES
MOUNTING BRACKET
INSTALLED FOR
19-IN. (48.26 CM)
RACK MOUNTING