AEG PROTECT 1.100 Power Supply User Manual


 
11
The greatest possible supply reliability of connected loads is
attained by the parallel connection of up to max. three
PROTECT 1. UPS systems. The n+x technology thus
guarantees maximum reliability through up to double active
redundancy on the one hand as well as on the other hand the
possibility of increased power with simple redundancy or even
only higher UPS power without any redundancy. The relationship
between the available output power and the degree of active
redundancy can be seen in the following overview:
Parallel system with PROTECT 1.100
Number of UPS units
Available power
1 2 3
0 10 kVA 20 kVA 30 kVA
1 --- 10 kVA 20 kVA
Active
redundancy
degree
2 --- --- 10 kVA
Parallel system with PROTECT 1.150
Number of UPS units
Available power
1 2 3
0 15 kVA 30 kVA 45 kVA
1 --- 15 kVA 30 kVA
Active
redundancy
degree
2 --- --- 15 kVA
Parallel system with PROTECT 1.200
Number of UPS units
Available power
1 2 3
0 20 kVA 40 kVA 60 kVA
1 --- 20 kVA 40 kVA
Active
redundancy
degree
2 --- --- 20 kVA